Kian Tajhiz’s medium’s voltage GIS uses SF6 gas as its insulating material and includes circuit breaker, disconnector, and earthing switch in a sealed container for maximized reliability and safety.


Features


  • Best technology
    • Adopts GIS technology accumulated from constructing a wide range of devices with wide ranges of voltage and current requirements

  • Abundant 22kV GIS supply record

  • Reliable components
    • Uses a spacer with AL2O3 material which has high-insulation characteristics
    • Uses tulip contactor which has proven its quality in the ultra-high voltage utility
    • Highly reliable VI is used

  • Excellent construction capability
    • Various construction experiences
    • Specialized engineers (Solution Execution Team)
    • Quality assurance guaranteed from construction to maintenance

With rated voltage of 24~38kV, rated current of 1,250~3,150A, and maximum breaking current of 40kA, Kian Tajhiz ’s ProGIS is designed and manufactured to meet various specifications. We have acquired IEC, ANSI, and various international certifications to provide the optimal product that satisfies the global customer’s demands.


Features


  • Safety is considered the top priority
    • Partitioning structure by bay
      Utilizes the partitions between the gas bays to prevent accidents in part of the facility from spreading to the entire facility.
    • 9T iron enclosure (VCB 28T)
      Uses an iron enclosure which has a melting point higher than an aluminum enclosure; risk of the enclosure melting by the internal arc is eliminated, and damage to the peripherals and human accidents are prevented.
    • Minimum gas pressure of 0.7kgf/cm2·G
      Pressure is maintained so that the risk of gas leakage, which may occur when gas pressure is high, is minimized.
    • Bellows installed at the tank connection unit
      Bellows maintain the mechanical safety of the system by absorbing the temperature change, errors in assembly, differences in the concrete base, and excessive displacement due to an earthquake.

    • Passed the Internal Arc Test
      Kian Tajhiz’s medium-voltage GIS was the first domestic manufacturer to pass the internal arc test in the medium voltage sector, reconfirming its high user safety.

  • Convenience of users considered
    • Modulization of each unit
      Modulization of the busbar, circuit breaker, DS/ES, and PNL units allows for fast disassembly with minimum replacement of parts.
    • Uninterrupted power expansion
      Double busbar GIS can be expanded with uninterrupted power.

  • First domestic design technology
    • Based on the technical know-how accumulated by developing ultra high-voltage GIS such as 362kV and 800kV, Kian Tajhiz  developed its GIS with state-of-the-art design technology such as
      three-dimentional electromagnetic field analysis, structure analysis, and thermal distribution analysis.

  • Highly reliable products made from highly reliable materials
    • AI 2 O 3 (Alumina Oxide) insulation spacer
      The general epoxy filler includes Si, so when the SF6 gas meets with oxygen and moisture, they create a chemical reaction and the dielectric strength cannot be maintained. The AI 2 O 3 solves this problem.
    • Tulip contactor used for 154kV or higher
      Tulip contactor is used for easy installation and removal and solid contact.

Specifications


Specification
Specification
Model
ProG 20625 S ProG 21225 S ProG 22025 S ProG 20625 D ProG 22025 D ProG 21240 ProG 22540 ProG 23040 ProG 23140 ProG 31231 ProG 32531
Rated voltage(kV) 25.8 25.8 25.8 25.8 25.8 24 24 24 24 36 36
Rated current (A) 630 1,250 2,000 600 2,000 1,250 2,500 3,000 3,150 1,250 2,500
Rated
short-circuit
breaking current
(kA)
25 25 25 25 25 40 40 40 40 31.5 31.5
Rated break
time(Cycle)
5 5 5 5 5 5 5 5 5 5 5
Power frequency
withstand voltage (kV)
70
(77)
70
(77)
70
(77)
70
(77)
70
(77)
70
(77)
70
(77)
70
(77)
70
(77)
70
(80)
70
(80)
Lightning impulse
withstand voltage (kV)
150
(165)
150
(165)
150
(165)
150
(165)
150
(165)
150
(165)
150
(165)
150
(165)
150
(165)
170
(195)
170
(195)
Operation method Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Motor driven
/Manual
Width (mm) 550 550 600 600 600 700 700 700 700 600 600
Height (mm) 2,350 2,350 2,350 2,600 2,600 2,350
/2,700
2,350
/2,700
2,350
/2,700
2,350
/2,700
2,350 2,350
Depth
(mm)
1,200 1,200 1,200 2,000 2,000 2,090 2,090 2,500 2,500 1,800 1,800
Rated
gas pressure
(kgf/㎠▪G)
1 1 1 1 1 1 1 1 1 1 1
Minimum
gas pressure
(kgf/㎠▪G)
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
Section view
Note: Vales in the parenthesis are for the withstand voltage between DS poles
Note: The S and D at the end of the model name represent single or double bus

For the first time domestically, Kian Tajhiz’s ChanGIS passed the arc resistance test (International Arc) and its reputation as for quality, performance, and stability have spread to global customers. In addition to its numerous advantages, the ChanGIS is offered at a competitive price, making it optimal for buildings, condominiums, factories, public facilities, PV power facilities, and wind power facilities.

 

Features

 
Section Switchgear ChanGIS
Width 100% 25%
Depth 100% 64%
Height 100% 100%
Area 100% 16%
  • Safety
    • Sealing of the charging unit reduces accidents.
  • High Reliability
    • Perfectly-sealed structure and excellent insulation material reduces the risk of accidents due to dielectric breakdown.
    • The live parts are perfectly sealed to eliminate short circuit and ground accidents and contamination of the parts.
    • Reliably manufactured by using a fixed frame for assembly
  • Easy Maintenance
    • Super-high pressure device is vacuumed and closed using the SF6 gas; providing easy maintainability due to low deterioration and abrasion levels. Socket-type epoxy holder allows easy socket replacement from the outside.
  • Cost Effectiveness
    • Compact structure reduces the installation area by 84 percent.
    • Smaller electricity room reduces the building costs.
 
Specification / Model ChanGIS
LBS CB MOF PT
Rated voltage (kV) 24
Rated current (A) 630 630 - -
Rated short-circuit
breaking current (kA)
25 25 - -
Rated break time (Cycle) - 5 - -
Power frequency withstand voltage (kV/60s) 50
Lightning impulse withstand voltage (kV) 125
Operating mechanism Motor driven, manual
Width (mm) 1,400
Length (mm) 1,600 (2,500 including case)
Height (mm) 2,600
Weight (kg) 2,370
Insulation SF6